8112 – 4 Optically Isolated Inputs/4 Form C Outputs
The SeaDAC Lite 8112 provides 4 optically isolated inputs and 4 SPDT Form C
relay outputs. Inputs can range from 5-30VDC and provide 300V isolation to ground,
while the Form C relays switch up to 60VDC @ 5A or 250VAC @ 6A. Each Form
C relay has a discrete common and includes normally-open and normally-closed
contact connections. Each pair of inputs shares a common. Status LEDs display I/O
activity and field wiring is simplified via 3.5mm field removable terminal blocks.
8112-KT iPorthole
8112-OEM
Inputs
Type: 4 non-polarized optically isolated inputs
Voltage Range: 5-30VDC
Isolation: 300V
Input Resistance: 6.2K Ohms in series
Response Time: 4μs
Outputs
Type: 4 SPDT Form C relays
Power: DC 240W / AC 1200 VA
Contact Voltage: 60VDC / 250VAC max.
(5VDC min.)
Contact Current (DC): <30 VDC @ 5A max.
>30 VDC @ 700mA max.
(100mA min.)
Contact Current (AC): 6A max.
Operate Time: 10ms max.
Release Time: 5ms max.